Every machine tool is also an electrical machine: the spindle is a motor, the axes are driven by servomotors, the numerical control and the PLC operate at 24 V, and everything is powered by a 400 V control panel. In this chapter, we’ll cover the basics: current, voltage, and resistance; Ohm’s law and Kirchhoff’s laws; power and energy; magnetism; alternating current and the three-phase system; and transformers. Then we’ll look at how to measure these quantities and, most importantly, how to protect ourselves, all the way to reading a motor’s start-stop sequence diagram. One rule applies throughout the entire chapter: only authorized personnel may work inside control panels, and only when the system is de-energized.

44.1 Charge, Current, and Voltage

Matter is made up of atoms, and each atom has a positively charged nucleus surrounded by negatively charged electrons. In metals, the outermost electrons are loosely bound and can move from one atom to another; this is why metals are conductors. In plastics, rubber, glass, and ceramics, the electrons remain in place: these materials are insulators, and they are used to coat cables and separate live parts.

The electric charge Q is measured in coulomb (C). A coulomb is an enormous number of electrons: approximately 6.24 × 1018. When charges move in an orderly manner within a conductor, this results in a electric current; its intensity I It is the charge that passes through a cross-section of the wire in one second, and is measured in ampere (A).

Current Intensity
I = Qt Q = I · t
I current in A · Q load in C · t time in seconds. Batteries are rated in ampere-hours: 1 Ah = 1 A for 3,600 s = 3,600 C.

For charges to move, something must push them: voltage V (or potential difference), which is measured in volts (V). Voltage is the energy that the generator supplies to each coulomb that passes through it: 1 V = 1 J/C. A 12-volt battery supplies 12 joules per coulomb; the household electrical grid supplies 230 joules per coulomb.

The comparison with water is very helpful. The pump creates a pressure difference between the supply and return lines, and the water circulates through the circuit; the amount of water that passes through in one second is the flow rate. A narrow pipe slows down the water. In an electrical circuit, the generator creates voltage, the charges flow, the current is the “charge flow rate,” and the resistance is the narrow pipe.

pumppumps waterrestrictionflow ratehydraulic circuitgeneratordrives the loadsresistance Rcurrent I+Electrical circuitpump ↔ generator · pressure difference ↔ voltage Vwater flow rate ↔ current I · restriction ↔ resistance R
Figure 44.1 · The hydraulic analogy. Without a pump, water does not circulate; without voltage, current does not flow. If the pipe is broken, the flow stops in both circuits.

Direct Current and Alternating Current

If the voltage always has the same value and direction, it is called direct current (symbol ⎓ or DC): this is the type found in batteries and power supplies. If, on the other hand, the voltage continuously changes in both magnitude and direction, following a curve called a sine wave, it is called alternating current (symbol ~ or AC): this is the type used in the electrical grid, which in Europe operates at 50 cycles per second.

24 VtVdirect currentvalue and direction always the same+325 V−325 VtV50 Hz alternating currentchanges direction about a hundred times per second
Figure 44.2 · On the left, a 24 V DC voltage; on the right, the AC voltage from the power grid, which oscillates between +325 V and −325 V (see Section 44.9 for an explanation of these values).

A machine tool has both tools. The control panel receives a 400-volt three-phase AC supply, which powers the motors; a transformer and a power supply provide 24 volts DC for the PLC, the numerical control system, the sensors, the solenoid valves, and the contactor coils.

Example 44.1 · The charge supplied by a battery charger

A charger delivers 2 A for an hour and a half. How much charge goes into the battery?

t = 1,5 h = 1,5 · 3600 = 5400 s
Q = I · t = 2 · 5400 = 10 800 C
in ampere-hours: 2 A × 1.5 h = 3 Ah (and in fact, 3 × 3,600 = 10,800 C)
10,800 C = 3 Ah
💡
The direction of current flow. By convention, current flows out of the positive terminal of the generator, passes through the circuit, and returns through the negative terminal. Electrons actually flow in the opposite direction, but this convention was established before their discovery and has remained in use: all diagrams and formulas follow it.

44.2 Electrical Circuits and Ohm's Law

An electrical circuit is a closed path through which current can flow. It always consists of a power source (cell, battery, power grid, power supply), conductors (wires), one or more loads (lamps, motors, resistors, coils), and usually a control device (switch, button, contact) and a protective device (fuse, circuit breaker).

  • closed circuit: the path is complete and current flows;
  • open circuit: the path is interrupted (an open switch, a broken wire) and no current flows, even though voltage is present;
  • Short circuit: The two terminals of the generator come into contact through a resistance that is virtually zero; the current becomes extremely high, and without protection, the wires will melt or catch fire.

In schematics, each component is drawn with a standardized symbol. In Italy, the CEI EN 60617 standards apply, which are the same throughout Europe: anyone who learns to read them can understand schematics from any manufacturer. The figure shows the symbols we will use in this chapter.

+battery (continued)AC generatorresistorlight bulbNO (open) contactNC contact (closed)NO buttonfusecapacitorinductorrelay or contactor coilM3~three-phase motorprotective groundVvoltmeterAammeterthermal relay
Figure 44.3 · The most common symbols, in accordance with the CEI EN 60617 standards. NA = normally open (does not allow current to flow when in the rest position), NC = normally closed (allows current to flow when in the rest position).
VAI12 V battery+−switchlight bulbammeter (in series)voltmeter(in parallel)The current travels out of the positive terminal of the battery, passes through the light bulb, and travels back in through the negative terminal.
Figure 44.4 · A simple circuit. The ammeter is connected in series, that is, in the path of the current; the voltmeter is connected in parallel, between the two points whose voltage is to be measured.

The German physicist Georg Ohm discovered that in a metallic conductor, at a constant temperature, the current is directly proportional to the voltage: if the voltage doubles, the current also doubles. The ratio between voltage and current is constant and is called resistance R; it is measured in ohms (Ω).

Ohm's Law
V = R · I I = VR R = VI
V: voltage across the resistor, in V · R: resistance in Ω · I is the current in A. Convenient multiples: 1 kΩ = 1,000 Ω, 1 MΩ = 1,000,000 Ω, 1 mA = 0.001 A. With V in volts and R in kΩ, the current is directly given in mA.
Example 44.2 · The Three Forms of Ohm's Law

A 24-volt indicator light has a resistance of 48 Ω: How much current does it draw?

I = V / R = 24 / 48 = 0,5 A

A contactor coil, powered by 24 V DC, draws 0.2 A: What is its resistance?

R = V / I = 24 / 0,2 = 120 Ω

A current of 5 mA flows through a 2.2 kΩ resistor: What is the voltage across it?

V = R · I = 2200 · 0.005 = 11 V (or 2.2 kΩ · 5 mA = 11 V)
0,5 A · 120 Ω · 11 V
💡
Not everything follows Ohm's law. The law applies equally well to wires and resistors. A filament lamp, when cold, has a resistance ten times lower than when hot, and draws a peak current when turned on; diodes, LEDs, and transistors (Chapter 46) are not linear at all. For them R = V / I It applies only on a case-by-case basis.

44.3 Resistance and Resistivity

The resistance of a wire depends on three factors: the material, the length, and the cross-sectional area. A long wire offers more resistance than a short one, and a thick wire offers less resistance than a thin one—just as a wide pipe allows more water to flow through than a narrow one. The material is represented in the formula by its resistivity, ρ (rho).

Resistance of a Conductor
R = ρ · LS
R resistance in Ω · ρ resistivity in Ω · mm²/m (the practical unit for cables) · L Conductor length in meters · S cross-sectional area in mm². In the SI system, resistivity is expressed in Ω·m: 1 Ω·mm²/m = 10−6 Ω · m.
material with resistivity ρ(copper, aluminum, steel, etc.)L (m)cross-sectional area S(mm²)R = ρ · L / SDouble length:double resistancetwice the cross-sectional area:half the resistance
Figure 44.5 · Resistance increases with length and decreases with cross-sectional area.
Materialρ at 20 °C (Ω · mm²/m)α (1/°C)Where it is used
Silver0,0160,0038relay and switch contacts
Copper0,01750,0039cables, windings, busbars
Aluminum0,0280,0040large-diameter lines, motor enclosures
Brass0,070,0015terminals, plugs
Structural steel0,150,005structures, frames, rebar grounding conductors
Stainless steel0,720,001machine parts, braking resistors
Nickel-chromium1,10,0001heating elements

Approximate, rounded values: for steels, these vary significantly depending on the composition.

Example 44.3 · The Resistance of a Cable

A 2.5 mm² copper cable is 50 m long. What is the resistance of a single conductor? And what about the combined resistance of the supply and return lines? What if it were made of aluminum?

a conductor: R = 0.0175 × 50 / 2.5 = 0.35 Ω
The round trip is 100 m of file: R = 0.0175 · 100 / 2.5 = 0.70 Ω
aluminum, a conductor: R = 0.028 × 50 / 2.5 = 0.56 Ω (60% higher)
0.35 Ω per conductor, 0.70 Ω per full turn

The voltage drop across a line

Power cables are also resistors—small ones, but not zero. When current flows through them, a voltage is “lost” across them R · I, and the load receives less voltage than at the start. It is the voltage drop: If it is too high, the motors have trouble starting, the lights are dim, and the wires overheat. For consumer circuits, the goal is to stay within 4% of the rated voltage.

I = 13.04 A230 V0.28 Ω0.28 Ω40-meter-long line, 2.5 mm² copperforward + return = 80 m → 0.56 ΩLoad3 kW222.7 V0.56 × 13.04 = 7.3 V is lost in the line
Figure 44.6 · The circuit from Example 44.4: The two conductors are two resistors connected in series with the load.
Example 44.4 · Voltage Drop Across a Single-Phase Line

A 3-kW, 230-V heater is powered by a 40-meter run of 2.5-mm² copper wire. How much voltage is lost along the line? And with a 4-mm² wire?

Current (as a good approximation): I = P / V = 3000 / 230 = 13.04 A (the electrical power is given in section 44.4)
Total wire length: one way + return = 80 m → Rline = 0.0175 · 80 / 2.5 = 0.56 Ω
ΔV = Rlinea · I = 0.56 · 13.04 = 7.30 V
as a percentage: 7.30 / 230 × 100 = 3.2% → 230 − 7.3 = 222.7 V reaches the load
with 4 mm²: R = 0.0175 × 80 / 4 = 0.35 Ω → ΔV = 0.35 × 13.04 = 4.57 V = 2.0%
3.2% with 2.5 mm² (acceptable), 2.0% with 4 mm²
✅
How to Choose the Cross-Sectional Area. The cross-sectional area of a cable is chosen based on the current it can carry without overheating (the current-carrying capacity), the voltage drop, and protection against short circuits. This is the job of the system designer, using the tables provided in the standards: these calculations help explain why a longer cable needs to be thicker.

The Effect of Temperature

In metals, resistance increases with temperature. For relatively small changes, the increase is proportional to the change in temperature, with the coefficient α shown in the table. This is why a hot motor has higher resistance in its windings than a cold one, and why manufacturers estimate the temperature of the windings by measuring their resistance.

Resistance and Temperature
RT = R20 · (1 + α · ΔT)
RT = temperature resistance at T · R20 = resistance at 20 °C · α = temperature coefficient in 1/°C · ΔT = T − 20, in °C
Example 44.5 · The Coil That Generates Heat

One phase of a motor measures 2.0 Ω at 20 °C. What is the reading when the winding is at 80 °C?

ΔT = 80 − 20 = 60 °C
R80 = 2,0 · (1 + 0,0039 · 60) = 2,0 · 1,234 = 2,468 Ω
About 2.47 Ω: 23% higher than when the motor is cold

44.4 Power and Electrical Energy

The generator delivers V joules per coulomb, and I coulombs pass through in one second: the energy delivered in one second—that is, the power—is the product of V and I. Using Ohm's law, this same power can be expressed in two other ways, which are convenient when the resistance is known.

Electrical power
P = V · I P = R · I² P = V²R
P (power) in W · V in V · I in A · R in Ω. For alternating current, the first form applies only to resistive loads; in other cases, the power factor must be taken into account (Section 44.10).

In a resistor, all electrical energy is converted into heat: this is the Joule effect. It is useful in heating elements, heat-treatment furnaces (Chapter 22), and soldering irons; it is also useful in fuses, where a thin wire melts when the current exceeds the limit. On the other hand, it is a waste in cables, motors, and transformers, where it generates heat without performing any useful work. The formula R · I² reveals an important fact: doubling the current quadruples the heat.

Example 44.6 · A 2000-watt space heater

An electric space heater is rated at 2000 W at 230 V. What is its current draw, and what is its resistance?

I = P / V = 2000 / 230 = 8,70 A
R = V² / P = 230² / 2000 = 52 900 / 2000 = 26,45 Ω
Check: R · I² = 26.45 · 8.70² = 26.45 · 75.6 = 2000 W ✓
8,70 A e 26,45 Ω
Example 44.7 · How much heat does the line generate?

Based on Example 44.4 (0.56 Ω, 13.04 A), how much power is converted into heat in the cables?

Plost = R · I² = 0,56 · 13,04² = 0,56 · 170,1 = 95,3 W
or ΔV · I = 7.30 · 13.04 = 95.3 W
Approximately 95 W lost over a 40-meter run, or 3.2% of the heater's power

Energy and the kilowatt-hour

Energy is power times time. In the SI system, it is measured in joules, but for electricity, the kilowatt-hour (kWh) is used—the energy of 1 kW over one hour, equal to 3.6 MJ (Chapter 2). This is the unit shown on the meter and on the bill.

Electricity and Cost
E = P · t cost = E · price
And energy in kWh if P is in kW and t is in hours (in J if P is in W and t is in s) · price in €/kWh
Example 44.8 · How much does the compressor cost?

The workshop's compressor draws 3 kW and runs an average of 5 hours a day for 220 days a year. At an electricity rate of 0.25 €/kWh, how much does it cost per year? And how much do 20 36-W LED ceiling lights cost if left on for a weekend (60 hours)?

compressor: 3 kW · 5 h = 15 kWh per day; 15 · 220 = 3,300 kWh per year
cost: 3,300 × 0.25 = 825 € per year
lights: 20 × 36 W = 720 W = 0.72 kW; 0.72 × 60 = 43.2 kWh → 43.2 × 0.25 = 10.80 €
€825 per year for the compressor; €10.80 for a weekend of forgotten lights

44.5 Resistors in Series and in Parallel

Two or more resistors are in series when they are connected one after the other along the same path: the current is the same through all of them, and the generator’s voltage is divided among them. They are in parallel when they are connected to the same two points: they all have the same voltage, and the generator’s current is divided among them. The outlets in a home and the loads on a circuit breaker panel are connected in parallel: each receives the full voltage and operates even if the others are turned off.

Equivalent resistance
series: Req = R1 + R2 + R3 + ...
parallel: 1Req = 1R1 + 1R2 + 1R3 + ... only two: Req = R1 · (R2R1 + R2)
In a series circuit, the equivalent resistance is always greater than the largest resistance; in a parallel circuit, it is always less than the smallest resistance. Two resistors of equal value connected in parallel have a combined resistance equal to half that of a single resistor.
10 Ω22 Ω68 Ω2.4 V5.28 V16.32 VI = 0.24 A24 Vseriessame current in allR_(eq) = 100 Ω60 Ω0.4 A40 Ω0.6 A120 Ω0.2 A1.2 A24 Vparallelsame voltage across all · R_(eq) = 20 Ω
Figure 44.7 · The circuits from Examples 44.9 and 44.10. In series, voltages are divided; in parallel, currents are divided.
Example 44.9 · Three Resistors in Series

10-, 22-, and 68-Ω resistors connected in series across 24 V. What are the current and voltage across each one?

Req = 10 + 22 + 68 = 100 Ω → I = 24 / 100 = 0.24 A
V1 = 10 · 0,24 = 2,4 V; V2 = 22 · 0,24 = 5,28 V; V3 = 68 · 0,24 = 16,32 V
Check: 2.4 + 5.28 + 16.32 = 24 V ✓
0.24 A; the higher the resistance, the higher the voltage
Example 44.10 · Three Resistors in Parallel

60-, 40-, and 120-Ω resistors connected in parallel across 24 V. What are the equivalent resistance and currents?

1 / Req = 1/60 + 1/40 + 1/120 = 2/120 + 3/120 + 1/120 = 6/120 → Req = 20 Ω
Currents in the branches: 24 / 60 = 0.4 A; 24 / 40 = 0.6 A; 24 / 120 = 0.2 A
Total current: 0.4 + 0.6 + 0.2 = 1.2 A = 24 / 20 ✓
Req = 20 Ω, less than 40 Ω; total current 1.2 A
Example 44.11 · A mixed-signal circuit

A resistor R1 = 10 Ω is connected in series with the parallel combination of R2 = 30 Ω and R3 = 60 Ω; the entire circuit is powered by 12 V. What are the currents and voltages?

First, the parallel circuit: R23 = 30 · 60 / (30 + 60) = 1800 / 90 = 20 Ω
Then the series: Req = 10 + 20 = 30 Ω → I = 12 / 30 = 0.4 A
V1 = 10 × 0.4 = 4 V; 20 × 0.4 = 8 V remains across the parallel branch
I2 = 8 / 30 = 0.267 A; I3 = 8 / 60 = 0.133 A (total 0.4 A ✓)
Simplification always starts from the inside: first the parallel groups, then the series

The Voltage Divider

Two resistors connected in series divide the voltage into parts proportional to their values. By measuring the voltage across just one of the two resistors, you obtain a voltage lower than the original one: this is a voltage divider. It is used to match a signal to the input of an electronic circuit, and is found inside sensors and potentiometers (Chapter 47).

Voltage Divider
Vu = V · R2R1 + R2
Vu = output voltage, measured across R2 · V = input voltage · R1 = resistance toward the input · R2 = resistance toward zero. This formula applies in an open-circuit condition, that is, when the output is not powering anything.
+24 V0 VR1 = 3.9 kΩR2 = 1 kΩload10 kΩVuVu = V · R2 / (R1 + R2)open-circuit:24 · 1 / 4.9 = 4.90 Vwith the 10 kΩ load:the voltage drops to 4.54 V
Figure 44.8 · The voltage divider from Example 44.12. The load (shown as a dashed line) is connected in parallel with R2 and lowers the output voltage.
Example 44.12 · From 24 V to approximately 5 V

If R1 = 3.9 kΩ and R2 = 1 kΩ, what voltage is obtained from 24 V? And what if a 10 kΩ load is connected to the output?

open-circuit voltage: Vu = 24 · 1 / (3.9 + 1) = 24 / 4.9 = 4.90 V
with the load: R2 and the load are in parallel: 1 · 10 / (1 + 10) = 0.909 kΩ
Vu = 24 · 0,909 / (3,9 + 0,909) = 21,82 / 4,809 = 4,54 V
4.90 V open-circuit, 4.54 V under load: the voltage divider is fine for signals, but not for powering something that draws current

44.6 Kirchhoff's Laws and the Real Generator

When a circuit has multiple generators or multiple interlinked loops, series and parallel connections alone are not enough. You need Kirchhoff's two laws, which apply to any circuit.

  • Node Theorem. A node is a point where three or more files meet. Charges do not accumulate: the sum of the currents entering a node is equal to the sum of the currents leaving it.
  • Mesh Law. A mesh is a closed path within the circuit. When tracing a path along a mesh, the sum of the voltages across the generators is equal to the sum of the voltage drops R · I across the resistors.
Kirchhoff's Laws
nodes: Σ Inewcomers = Σ Ioutgoing mesh: Σ E = Σ R · I
Σ means “sum of” · E is the voltage across the generators in the loop, positive if it pushes in the chosen direction of current flow · R · I are the voltage drops across the resistors, positive if the current flows in the chosen direction. The directions of the currents can be chosen arbitrarily: if a current is negative, simply reverse its direction.
R1 = 4 ΩE1 = 24 VR2 = 2 ΩE2 = 12 VR3 = 6 Ω++ABI1I2I3Stitch 1stitch 2
Figure 44.9 · Two generators together power resistor R3. The red arrows indicate the chosen directions of the currents, and the blue arrows indicate the directions of the loops.
Example 44.13 · Two meshes solved using a single system

In the circuit shown in Figure 44.9, E1 = 24 V with R1 = 4 Ω, E2 = 12 V with R2 = 2 Ω, and R3 = 6 Ω. Find the three currents.

Node A: I3 = I1 + I2
Loop 1 (E1, R1, R3): 24 = 4 · I1 + 6 · (I1 + I2) → 24 = 10 · I1 + 6 · I2
loop 2 (E2, R2, R3): 12 = 2 · I2 + 6 · (I1 + I2) → 12 = 6 · I1 + 8 · I2
From the first equation, by substitution (Chapter 1): I1 = (24 − 6 · I2) / 10 = 2.4 − 0.6 · I2
In the second equation: 6 · (2.4 − 0.6 · I2) + 8 · I2 = 12 → 14.4 + 4.4 · I2 = 12 → I2 = −2.4 / 4.4 = −0.545 A
I1 = 2,4 − 0,6 · (−0,545) = 2,727 A; I3 = 2,727 − 0,545 = 2,182 A
Check for cell 2: 2 · (−0.545) + 6 · 2.182 = −1.09 + 13.09 = 12 V ✓
I1 = 2.73 A, I2 = −0.55 A, I3 = 2.18 A. The negative sign indicates that in E2, the current flows into the positive terminal: the 24-V generator is charging the 12-V generator.

The Real Generator

An ideal generator would always produce the same voltage, regardless of the current demanded of it. A real generator has a small internal resistance, Ri: when it supplies current, part of the voltage is lost internally, and less voltage reaches the terminals. The voltage when there is no load is called the electromotive force, E.

Real Generator
V = E − Ri · I I = ERi + R Icc = ERi
V voltage at the terminals · E electromotive force (open-circuit voltage) in V · Ri internal resistance in Ω · R load resistance · Icc short-circuit current, with the terminals connected to each other
E = 12.6 VRiactual generatorloadVI10 A → 12.0 V12.6 V210 A0I (A)V (V)V = E − Ri · Ithe voltage dropswhen the current increases
Figure 44.10 · On the left is the model of the actual generator; on the right is its characteristic curve: the voltage across the terminals decreases linearly with current, dropping to zero during a short circuit.
Example 44.14 · The internal resistance of a battery

A 12 V battery measures 12.6 V when open-circuit and 12.0 V when delivering 10 A. What is its internal resistance? What current would it supply in a short-circuit condition?

Ri = (E − V) / I = (12,6 − 12,0) / 10 = 0,06 Ω
Icc = E / Ri = 12.6 / 0.06 = 210 A
with a 1 Ω load: I = 12.6 / (0.06 + 1) = 11.89 A and V = 1 · 11.89 = 11.89 V
Ri = 0.06 Ω; short-circuit current 210 A, enough to red-hot a wrench resting on the poles

44.7 Capacitors and Inductors

A capacitor consists of two conductive surfaces, called plates, separated by an insulator. When connected to a voltage, it accumulates a positive charge on one plate and a negative charge on the other, and retains these charges even when disconnected. The accumulated charge is proportional to the voltage; the ratio between the two is the capacitance C, which is measured in farads (F). A farad is an extremely large unit: in practice, microfarads (1 µF = 10−6 F) and nanofarads are used.

Capacitor
Q = C · V τ = R · C vC = V · (1 − e−t/τ)
Q charge in C · C capacitance in F · V charging voltage in V · τ (tau) time constant in s, with R in Ω · vC voltage across the capacitor after a time t from the start of charging · e = 2.718 is the base of the natural logarithm (ex key on the calculator)

A capacitor does not charge instantly. If it is charged through a resistor R, the voltage rises rapidly at first and then more and more gradually, following an exponential curve. The characteristic time is the time constant τ = R · C: after τ, the capacitor is at 63% of its final voltage; after 3τ, at 95%; after 5τ, at 99%; and it is considered fully charged. Discharging follows the inverse curve: after τ, 37% of the voltage remains.

241 s = τ2 s3 s4 s5 sτ: 15.2 V (63%)3τ: 22.8 V (95%)5τ: 23.8 V (99%)The tangent at the origin reaches 24 V exactly after τtvC(V)
Figure 44.11 · The charge on the capacitor in Example 44.15 (R = 10 kΩ, C = 100 µF, τ = 1 s) when a 24 V voltage is applied.
Example 44.15 · The time constant

A 100 µF capacitor is charged to 24 V through a 10 kΩ resistor. Calculate τ, the voltage after 1 s and after 5 s, the time it takes to reach 12 V, and the final charge.

τ = R · C = 10 000 · 0,0001 = 1 s
After 1 s: vC = 24 · (1 − e−1) = 24 · (1 − 0.368) = 24 · 0.632 = 15.17 V
After 5 s: vC = 24 · (1 − e−5) = 24 · 0.9933 = 23.84 V
at half voltage: 1 − e−t/τ = 0.5 → t = τ · ln 2 = 1 · 0.693 = 0.693 s
Final charge: Q = 0.0001 × 24 = 0.0024 C = 2.4 mC
τ = 1 s; 15.2 V after 1 s, 23.8 V after 5 s; half the voltage after 0.69 s

Capacitors are found in power supplies, where they smooth out the voltage; in timing circuits; on single-phase motors, to start them; and in power factor correction panels (section 44.10). And in frequency converters (inverters, Chapter 45), which contain large capacitors charged to more than 500 V.

⚠️
The capacitor remains charged. A capacitor retains its charge even when the machine is turned off and disconnected. The nameplates on inverters indicate how many minutes to wait before opening them, and the technician verifies with a meter that the voltage has indeed dropped. This is one of the reasons why work inside control panels is performed only by qualified personnel.

The inductor, as a brief mention

An inductor is a coil of file, often wound around an iron core. It behaves in the opposite way to a capacitor: it resists changes in current. When it is energized, the current rises slowly, with a time constant τ = L / R; when the circuit is opened, the coil tries to maintain the current and produces a voltage spike that can cause sparks at the contacts and damage electronic components. For this reason, the coils of DC relays and solenoid valves have a diode connected in parallel, while those for AC have an RC filter (Chapters 46 and 49). Inductance L is measured in henry (H).

44.8 Magnetism and Electromagnetism

A magnet has two poles, north and south: like poles repel each other, and opposite poles attract each other. A magnetic field surrounds the magnet, represented by a drawing of lines that emerge from the north pole and return to the south pole; where the lines are dense, the field is strong. The strength of the field is measured by the magnetic induction B, in tesla (T): between the poles of a motor, it reaches about 1 T, while a refrigerator magnet has a few hundredths of a tesla.

In 1820, it was discovered that an electric current also creates a magnetic field around the wire. When the wire is wound into a coil, the magnetic lines of force add up, and the coil behaves like a magnet that turns on and off with the current. This gives rise to two effects that drive the entire world of electricity.

  • Force on a conductor. A current-carrying wire placed in a magnetic field experiences a force that is perpendicular to both the wire and the field. This is the principle of the engine: The rotor's slots contain conductors through which current flows, and the forces generate torque.
  • Electromagnetic induction. A wire moving within a magnetic field, or a coil in which the field changes, generates a voltage across its ends. This is the principle behind the generator (and, as we will see, the transformer). The direction of the induced voltage is always such that it opposes the cause that produced it: a generator under load slows down whatever is causing it to rotate.
Force on a Conductor and Induced Voltage
F = B · I · L e = B · L · v
F = force in N · B = magnetic induction in T · I = current in A · L = length of the conductor immersed in the field, in m · e = induced voltage in V · v = velocity of the conductor, perpendicular to the field, in m/s. These formulas apply when the wire, the field, and the velocity are perpendicular to each other.
NSBFprinciple of the motorcurrent + magnetic field → forceF = B · I · LNSBvprinciple of the generatormotion + magnetic field → voltagee = B · L · v
Figure 44.12 · A cross-sectional view of the wire: the dot indicates current flowing out of the page, and the cross indicates current flowing into the page. On the left, the current in the magnetic field produces a force; on the right, the wire moved through the magnetic field becomes the path of an induced current flowing in the opposite direction.
Example 44.16 · Force and tension in a 0.8 T field

A 0.15 m-long conductor in a 0.8 T magnetic field carries a current of 20 A. What force acts on it? If, instead, it is moved at 10 m/s without current, what voltage is induced?

F = B · I · L = 0,8 · 20 · 0,15 = 2,4 N
e = B · L · v = 0,8 · 0,15 · 10 = 1,2 V
2.4 N and 1.2 V: To achieve the required torque and voltage, the motors have dozens of conductors connected in series and in parallel

Electromagnets, Relays, and Contactors

A coil wound around a soft-iron core is an electromagnet: when current flows through it, it attracts iron; when the current is off, it repels it. Solenoid valves in pneumatics and hydraulics (Chapters 42 and 43), motor brakes, and the magnetic plates in grinders all work this way.

The relay uses an electromagnet to move contacts. The coil, powered by a small current (often 24 V), attracts a movable armature that shifts the common contact C: at rest, C touches the NC contact; when the coil is energized, it switches to the NO contact. In this way, a low-voltage control circuit turns another, separate circuit on and off. A contactor is a heavy-duty relay with three power contacts capable of controlling a motor and several auxiliary contacts for control signals.

electromagnetNSWhen an electric current passes through it, iron becomes a magnetrelayNCNACA1A2springarmaturecore and coilAt rest, C touches NC; when the coil is energizedthe armature moves down and C switches to NO
Figure 44.13 · On the left is an electromagnet; on the right is a relay viewed from the side. A1 and A2 are the coil terminals, as shown in the diagrams.

44.9 Sinusoidal Alternating Current

A generator that rotates a coil within a magnetic field produces a voltage that rises, falls, changes polarity, and returns, following a sine wave. This is the waveform of the line voltage. There are only a few parameters that describe it.

  • the period T, the duration of a complete cycle, in seconds;
  • the frequency f, the number of cycles per second, in hertz (Hz): in Europe, the power grid operates at 50 Hz; in North America, at 60 Hz;
  • the peak value Vp, the maximum value reached;
  • the effective value V, the value of the DC voltage that would heat a resistor in the same way. This is the value we always refer to: “230 V” is an effective value, and it is what multimeters measure.
Amplitudes of the Sine Wave
f = 1T ω = 2π · f v = Vp · sin(ω · t ) V = Vp√2
f frequency in Hz · T period in s · ω frequency in rad/s · v instantaneous value at time t · Vp peak value · V effective value. The same relationships hold for current: I = Ip / √2.
+325+2300−325RMS value 230 Vpeak voltage Vp = 325 V10203040period T = 20 ms (50 Hz)t (ms)v (V)
Figure 44.14 · Two periods of the line voltage. The peak is 325 V; the root-mean-square (RMS) value—commonly referred to as “230 V”—is the peak divided by √2.
Example 44.17 · Peak, Period, and Frequency of the Network
period: T = 1 / 50 = 0.02 s = 20 ms
frequency: ω = 2 × 3.1416 × 50 = 314.16 rad/s
230 V peak: Vp = 230 · √2 = 230 · 1.4142 = 325.3 V; peak-to-peak: 650.5 V
Peak voltage of 400 V: 400 × 1.4142 = 565.7 V
20 ms, 314 rad/s, 325 V peak: the insulation must withstand the peak voltage, not the rms value

Resistive, Inductive, and Capacitive Loads

Each load behaves differently, depending on its nature.

  • Resistive load (light switches, ovens, incandescent lamps): the current follows the voltage instant by instant; it is said to be in phase.
  • Inductive load (motors, transformers, coils, reactors): The coil dampens fluctuations, and the current lags behind the voltage. The coil presents an inductive reactance XL that increases with frequency.
  • Capacitive load (capacitors): The current leads the voltage; the capacitive reactance XC decreases as the frequency increases.

The lag or lead is measured by the phase angle φ (phi), in degrees: a full cycle is 360°. A real load, such as a motor, is somewhat resistive and somewhat inductive: the current lags by an angle between 0° and 90°. The ratio of the rms voltage to the rms current is called impedance Z, in ohms.

Reactances and Impedance
XL = 2π · f · L XC = 12π · f · C Z = VI
XL, XC, Z in Ω · f in Hz · L inductance in H · C capacitance in F · V, I rms values
φ = 37°: the current arrives afterinductive load, so φ = 0.8voltage vcurrent it
Figure 44.15 · In an inductive load, the current passes through zero and reaches its peak after the voltage does. With cos φ = 0.8, the delay is 37°, or approximately 2 ms at 50 Hz.
Example 44.18 · An Inductor and a Capacitor Connected to the Power Grid

What is the current, at 230 V and 50 Hz, flowing through an ideal 0.1 H coil? And through a 10 µF capacitor?

XL = 2 · 3.1416 · 50 · 0.1 = 31.42 Ω → I = 230 / 31.42 = 7.32 A, lagging by 90°
XC = 1 / (2 · 3.1416 · 50 · 0.000 01) = 1 / 0.003 142 = 318.3 Ω → I = 230 / 318.3 = 0.723 A, leading by 90°
7.32 A in the coil, 0.72 A in the capacitor. At 100 Hz, the coil would allow half the current to pass through, and the capacitor twice as much.

44.10 AC Power and Power Factor

When current and voltage are out of phase, the product V × I is no longer entirely useful work. A portion of the energy flows back and forth between the grid and the magnetic fields of the coils (or capacitors) without being converted into work or heat. Thus, three types of power are distinguished.

  • active power P, in watts (W): the power that is actually converted into mechanical work or heat, and which the meter measures in kWh;
  • reactive power Q, in reactive volt-amperes (var): the power needed to create the magnetic fields in motors and transformers, which is fed back;
  • apparent power S, in volt-amperes (VA): the product of the effective voltage and current. Cables, circuit breakers, transformers, and generators are sized based on this value, because they are the components that carry the current.
Single-Phase Power Ratings
S = V · I P = V · I · cos φ Q = V · I · sin φ S = √(P² + Q²)
S in VA · P in W · Q in var · V, I effective values · cos φ power factor, between 0 and 1: it is 1 for a resistive load, between 0.7 and 0.9 for a motor under full load, and much lower for a motor running at no load
φP = 1840 W (active)Q = 1,380 var(reactive)S = 2,300 VA (apparent)Q' = 605 var after power factor correctionS² = P² + Q²P = S · cos φQ = S · sin φ
Figure 44.16 · The power triangle from Example 44.19, to scale. The dashed line represents the apparent power after power factor correction: the active power remains the same, while the reactive and apparent powers decrease.

A low power factor is a problem: for the same active power, the current is higher, so the cables get hotter, voltage drops increase, and the substation transformer reaches its capacity sooner. For this reason, the utility charges for reactive power when the average power factor falls below the values established by the electric utility’s regulations. The solution is power factor correction: capacitors are connected in parallel with the inductive loads. The capacitors absorb reactive power of the opposite sign and supply it “on the spot” to the motors, so less current passes through the grid. In industrial settings, power factor correction is usually performed using an automatic control panel that connects the capacitors in stages.

Example 44.19 · Power Ratings of a Single-Phase Motor and Power Factor Correction

A single-phase motor draws 10 A at 230 V with cos φ = 0.8. Calculate S, P, and Q. What kind of capacitor is needed to bring cos φ to 0.95, and how much current will it draw afterward?

S = 230 × 10 = 2,300 VA
P = 2300 × 0.8 = 1840 W; sin φ = √(1 − 0.8²) = 0.6 → Q = 2300 × 0.6 = 1380 var
then: tan φ' = tan(arccos 0.95) = 0.3287 → Q' = P · tan φ' = 1840 · 0.3287 = 605 var
The capacitor must provide QC = 1380 − 605 = 775 var
capacitance: C = QC / (ω · V²) = 775 / (314.16 · 230²) = 775 / 16,619,000 = 0.000 046 6 F = 46.6 µF
New current: I' = P / (V · cos φ') = 1840 / (230 · 0.95) = 8.42 A
S = 2300 VA, P = 1840 W, Q = 1380 var; with approximately 47 µF, the current drops from 10 A to 8.42 A, and the motor operates exactly as before

44.11 The Three-Phase System

The power grid carries not just one alternating voltage but three, generated by a generator with three windings shifted by 120°. The three voltages have the same frequency and the same magnitude, but they are out of phase by 120° relative to each other, that is, by one-third of a period: 20 / 3 = 6.67 ms. They travel along three phase conductors, L1, L2 e L3, plus a conductor of neutral N grounded in the cabin, and a PE protective conductor.

120° = 6.67 msL1L2L3tAt any given moment, the sum of the three voltages is zero.
Figure 44.17 · The three phase voltages. When one is at its maximum, the other two are negative and offset it.

The voltage between a phase and the neutral is 230 V; the voltage between two phases is 400 V. The ratio between the two is not 2, because the voltages are out of phase: it is √3 = 1.732. Three-phase power has two major advantages: it transmits more power using the same amount of copper, and it produces a rotating magnetic field in motors that allows them to start and run on their own, without capacitors or brushes (Chapter 45).

Three-Phase Voltages
VL = √3 · VF 400 V ≈ 1,732 · 230 V
VL: phase-to-phase voltage (between two phases) · VF: phase-to-neutral voltage (between phase and neutral)
Example 44.20 · From 230 to 400 V and back
230 · 1.732 = 398.4 V, which rounds to 400 V (the European nominal voltage)
400 / 1,732 = 230,9 V ≈ 230 V
Peak voltage of the series circuit: 400 · √2 = 565.7 V
Phase-to-neutral 230 V, phase-to-phase 400 V, with peaks of 566 V between phases

Star and Delta Connections

Three identical loads—for example, the three windings of a motor or the three heating elements of an oven—can be connected to the power grid in two ways.

  • Star (Y) connection: The three loads share one end (the star point, which can be connected to the neutral) and have their other ends connected to a phase. Each load receives the phase voltage, 230 V; the line current is equal to the load current.
  • Triangular (Δ): Each load is connected between two phases. Each load receives the phase-sequence voltage, 400 V; the line current is √3 times the load current.
L1L2L3Nstar (Y)across each load 400 / √3 = 230 Vline current = phase currentL1L2L3delta (Δ)400 V across each loadline current = √3 · phase current
Figure 44.18 · The same three loads connected in star and delta configurations on a 400-volt power system.
Example 44.21 · The Resistors in a Star-Delta Oven

An oven has three 46 Ω heating elements. What is the current and power drawn from a 400 V power source when the oven is connected in a star configuration and when it is connected in a delta configuration?

stella: Each resistor has 400 / 1.732 = 230.9 V → I = 230.9 / 46 = 5.02 A, which is equal to the line current
power per star: 3 · 230.9² / 46 = 3,478 W ≈ 3.5 kW
triangle: each resistor has 400 V → Iphase = 400 / 46 = 8.70 A; line current 8.70 × 1.732 = 15.06 A
Power in a delta configuration: 3 × 400² / 46 = 10,435 W ≈ 10.4 kW
In a delta connection, the power is three times that of a star connection. This is the same principle as the star-delta starting of motors (Chapter 45).

Three-Phase Power

Three-Phase Power (Balanced Load)
P = √3 · V · I · cos φ Q = √3 · V · I · sin φ S = √3 · V · I
V phase-to-phase voltage (400 V) · I line current · These formulas apply to both star and delta connections. For a motor, P is the power drawn from the grid: the rated power is the power delivered to the shaft, and the two are related by the efficiency, Presa = η · Passorbita (Chapter 9).
Example 44.22 · The current in a 7.5-kW motor

A 7.5 kW three-phase asynchronous motor (shaft power) operates at 400 V with an efficiency of η = 0.90 and a power factor of cos φ = 0.84. What is its current draw at full load?

Power consumption: Pa = 7500 / 0.90 = 8333 W
I = Pa / (√3 · V · cos φ) = 8333 / (1.732 · 400 · 0.84) = 8333 / 582.0 = 14.3 A
apparent power: S = 8333 / 0.84 = 9921 VA ≈ 9.9 kVA; motor losses: 8333 − 7500 = 833 W
Approximately 14.3 A per phase: this is the value at which the thermal relay is set (paragraph 44.14)
🎨
The Colors of the Conductors. For cables, the CEI EN 60445 standard assigns the yellow-green only to the PE protective conductor and the light blue to neutral; brown, black, and gray are used for the phases. In machine control panels, CEI EN 60204-1 recommends black for power, red for AC controls, dark blue for DC controls, and theorange For circuits powered from an external source that remain energized even when the main disconnect switch is open. The color is helpful, but it is never definitive proof: voltage must always be verified with a meter.

44.12 The Transformer and Measuring Instruments

A transformer changes the value of an alternating voltage. It consists of two windings—the primary and the secondary—wound around the same iron-sheet core and insulated from each other. The alternating current in the primary winding creates a magnetic flux in the core that changes continuously; this flux also passes through the secondary winding and, by induction, induces a voltage there. Each turn has the same induced voltage, so the voltages are in the same ratio as the number of turns. With direct current, the flux does not change and the transformer does not function.

Ideal Transformer
k = V1V2 = N1N2 = I2I1 S = V1 · I1 = V2 · I2
k transformation ratio · V1, V2 primary and secondary voltages · N1, N2 number of turns · I1, I2 currents · S apparent power in VA, as indicated on the nameplate. The actual transformer loses a few percent as heat; for a first approximation, this is neglected.
flux ΦV1 = 400 VN1 = 800 turnsV2 = 24 VN2 = 48 turnsprimarysecondaryV1 / V2 = N1 / N2 = 800 / 48 = 16.7
Figure 44.19 · The auxiliary circuit transformer from Example 44.23: many turns on the 400-V primary winding, few on the 24-V secondary winding.
Example 44.23 · The 400/24 V transformer for the auxiliary circuits

In a machine, a 250 VA transformer connected between two phases supplies 24 V AC to the control circuits. The primary winding has 800 turns. Calculate the turns ratio, the number of turns in the secondary winding, and the full-load currents.

k = 400 / 24 = 16,67
N2 = N1 / k = 800 × 24 / 400 = 48 turns
I2 = 250 / 24 = 10,42 A; I1 = 250 / 400 = 0,625 A
k = 16.7; 48 turns; 10.4 A on the secondary and just 0.63 A on the primary: where the voltage drops, the current rises

In machine control panels, the auxiliary transformer serves two purposes: it steps down the voltage and isolates the control circuits from the mains. This ensures that any malfunction involving the buttons or limit switches occurs at 24 V—a much less dangerous voltage—and that the circuit has its own controlled ground connection.

The multimeter and the clamp meter

A multimeter (or tester) measures voltage, current, and resistance—both DC and AC—and usually also checks for continuity in a wire by emitting an audible signal. The way you connect it depends on the quantity being measured, and connecting it incorrectly can be dangerous.

  • Voltage (V⎓ or V~): The probes should be placed on the two points between which you want to measure the voltage—that is, in parallel. The voltmeter has a very high internal resistance (several MΩ) and does not interfere with the circuit.
  • Current (A): Open the circuit and connect the meter in series, with the red probe in the current terminal. The ammeter has an internal resistance that is virtually zero.
  • Resistance (Ω) and continuity: The component must be de-energized; it is best to disconnect it from the rest of the circuit; the meter uses its internal battery.
voltagein parallel, circuit onVcurrentin series, open circuitAresistancecomponent disconnected and turned offΩR to be measured
Figure 44.20 · How to connect a multimeter: in parallel for voltage, in series for current, and with the circuit turned off for resistance.

The current collet measures alternating current (and, with the appropriate models, direct current as well) without breaking the circuit: the jaws clamp around the wire and detect the magnetic field that the current creates around it. The collets must clamp only a single conductor: if they clamp both the live wire and the neutral wire together, the two currents are equal and opposite, and the collet meter reads zero. It is the right tool for checking how much power a motor draws.

Example 44.24 · The error caused by the tester connected in parallel to the network

A multimeter was left with its probes in the current terminals, and someone plugged it into a 230 V outlet to “see if there’s voltage.” The internal resistance in that position, including the probes, is about 0.1 Ω. How much current would it draw?

I = V / R = 230 / 0,1 = 2300 A
Basically, the current is limited by the line, but it's still a short circuit: the tester's fuse blows, or—if it's not suitable—an arc forms in the operator's hand.
An ammeter connected in parallel is a short circuit. Before taking any measurement, check the selected function and the test lead sockets.
⚠️
The right tool. Multimeters are labeled with a measurement category (CAT II, CAT III, CAT IV) and the maximum voltage: at least CAT III is required for use on distribution panels. Never use stripped test leads, fuses replaced with wire, or hobby-grade tools on distribution panels. And live measurements inside a panel may only be performed by personnel who are trained and authorized for that work.

44.13 Electrical Safety

Electric current that travels through the human body disrupts the muscles and the heart—which function using small electrical signals—and burns tissue. The extent of the damage depends primarily on theintensity of the current and from the duration, then by the path (the hands and feet pass through the heart) and by the frequency. The table provides an idea of the thresholds for 50-Hz alternating current.

Electric Current in the BodyTypical Effects
about 0.5 mAthreshold of perception: a tingling sensation
about 10 mArelease threshold: above this value, the muscles contract and you can no longer lift your hand
20–30 mAcontraction of the chest muscles, difficulty breathing if the contact continues
more than 50 mArisk of cardiac fibrillation, which increases the longer the contact lasts
more than 1 Astop of heart function, severe internal and external burns

Approximate and rounded values: Sensitivity varies from person to person and depending on the duration of contact.

The current that flows depends on the voltage and the body’s resistance, which is not constant: it decreases as the voltage increases, when the skin is wet or sweaty, and when there is a large contact area. For this reason, standards establish a limit for contact voltage: in ordinary environments, 50 V for alternating current and 120 V for direct current. Below these values, contact—even prolonged contact—is not considered dangerous.

Example 44.25 · Why 230 V Is Dangerous and 24 V Is Not

Using conservative estimates, at 230 V, the body’s resistance between the hands and feet can be estimated at around 1,000 Ω; at 24 V, with dry skin, around 3,000 Ω. How much current flows?

at 230 V: I = 230 / 1000 = 0.23 A = 230 mA
at 24 V: I = 24 / 3000 = 0.008 A = 8 mA
230 mA is nearly five times the fibrillation threshold; 8 mA remains below the discharge threshold. That is why the machines' control systems operate at 24 V.

Direct and Indirect Contacts

  • Direct contact: You touch a part that is live during normal operation, such as an exposed terminal or a stripped wire. Protection is provided by insulation, enclosures, barriers, physical distance, and locking control panels. The 30-mA ground-fault circuit interrupter (GFCI) provides an additional layer of protection.
  • Indirect contact: You touch a metal part—such as a motor housing, a control panel door, or a machine base—that is normally de-energized but has become energized due to a failure in the insulation. This is the most insidious type, because the person touching it has done nothing wrong. Protection is provided by grounding the metal parts in conjunction with a ground-fault circuit interrupter (GFCI).

Grounding connects all ground points, via the yellow-green PE protective conductor, to a grounding rod driven into the ground. If the live wire comes into contact with the chassis, the fault current finds a path to ground and returns to the substation; the ground-fault circuit interrupter detects this and breaks the circuit before anyone gets hurt.

LNRncabin grounddifferentialIΔn = 30 mAM3~Fault: Phase touches the housingRa = 20 Ω184 VgroundFault current Ig = 230 / (20 + 5) = 9.2 A
Figure 44.21 · A fault in a system with a grounded neutral in the substation (TT system, used for low-voltage loads). The fault current returns to the substation through the ground, and the enclosure remains energized until something breaks the circuit.
Example 44.26 · The Fault That the Circuit Breaker Doesn't Detect

In the case of Figure 44.21, the machine’s ground resistance is Ra = 20 Ω and the cabin’s ground resistance is Rn = 5 Ω. What current does the fault flow? What is the voltage across the housing? Will a 16 A circuit breaker trip?

Ig = 230 / (20 + 5) = 9.2 A (neglecting the resistance of the cables)
Chassis voltage relative to ground: V = Ra · Ig = 20 · 9.2 = 184 V
9.2 A is less than 16 A: the circuit breaker does not trip, and the load remains at 184 V
The 30-mA differential detects an imbalance of 9.2 A—three hundred times its threshold—and trips in a few hundredths of a second
Condition specified in the standards for TT systems: Ra · IΔn ≤ 50 V → with 30 mA, Ra ≤ 50 / 0.03 = 1667 Ω is sufficient
Without a ground fault circuit interrupter (GFCI), the machine would remain at 184 V; with a GFCI, the protection works even with a poor ground connection.

Residual Current Device (RCD) and Circuit Breaker

The ground-fault circuit interrupter (GFCI) routes all live conductors (phase and neutral, or the three phases and neutral) through an iron ring, the toroid. If everything is working properly, the incoming and outgoing currents are equal, and their magnetic fields cancel each other out. If part of the current leaks to ground—through a metal object or a person—the balance is lost: a current flow is generated in the toroid, a small winding detects it, and the circuit breaker trips. The 30 mA IΔn sensitivity is used as additional protection for people. The RCD has a test button labeled “T,” which should be pressed periodically: if it does not trip, it must be replaced.

The circuit breaker, on the other hand, protects cables and appliances from excessively high currents and has two trip mechanisms.

  • the thermal cut-off, a bimetallic strip that heats up and bends: it trips in response to overloads (currents slightly above the rated value), with the response time becoming shorter as the current increases;
  • The magnetic trip unit, a coil that attracts an armature: it responds to short circuits in a few thousandths of a second.
CurveMagnetic response (multiples of In)Typical Use
B3 to 5 timeslong lines, resistive loads, outlets
C5 to 10 timesGeneral-purpose, small motors, lighting
D10 to 20 timestransformers and motors with high inrush current

Earth-leakage circuit breakers and circuit breakers with thermal-magnetic protection serve two different purposes: the former protects people from electric shocks, while the latter protects the electrical system from overcurrents. They are often combined into a single device, the earth-leakage circuit breaker with thermal-magnetic protection. Fuses perform the same function as circuit breakers by melting: gG-type fuses protect circuits, while aM-type fuses are designed for motors, which draw five to eight times the rated current for a few seconds during startup.

IP Protection Ratings

The enclosures of control panels, motors, push-button panels, and sensors are marked with an IP code followed by two digits (CEI EN 60529 standard). The first digit indicates the degree of protection against the ingress of solid objects and contact with internal parts; the second digit indicates the degree of protection against water. An “X” in place of a digit means that test was not performed.

FigureFirst section: solid figuresSecond digit: water
0no protectionno protection
1objects larger than 50 mm (the back of the hand)drops falling vertically
2objects larger than 12.5 mm (a finger)drops with a slanted casing up to 15°
3objects larger than 2.5 mm (one tool)rain at an angle of up to 60° from the vertical
4objects larger than 1 mm (a wire)splashes from all directions
5dust-protected (a small amount of dust can enter without causing damage)water jets
6completely dust-proofpowerful jets
7temporary immersion
8continuous dive, under the specified conditions
9high-pressure, high-temperature jets
Example 44.27 · Reading an IP degree
IP20, open distribution panel: no fingers inside, no protection against water → must be installed inside a cabinet
IP54, a machine's electrical cabinet: protected against dust and splashes
IP65, control panel mounted on the machine: dust-tight, resistant to water jets (and machine washing)
IP67, inductive sensor near the cutting area: dust-free, withstands even temporary immersion in coolant
The closer you get to the workpiece and the coolant, the higher those two numbers must be
⛔
Who is authorized to work on the electrical system. According to CEI 11-27, electrical work may only be performed by individuals who have been trained and certified as qualified by the employer, and, as a general rule, only when the system is de-energized: disconnect the circuit, lock the disconnect switch with your personal padlock, verify the absence of voltage with a tester, and ground the circuit if necessary. The manual teaches you how to understand the electrical system, not how to work on it while it’s energized. If you’re not qualified, always call an electrician.

44.14 The Machine Tool's Electrical Panel

All of a machine’s electrical equipment originates from its control panel, which is designed in accordance with the CEI EN 60204-1 standard. As the current flows from the power grid to the motors, the same components are always encountered.

  • the main disconnect switch Q0, with the handle on the door: it cuts power to the entire machine and locks in the open position with a padlock, so no one can turn it back on during maintenance;
  • fuses and circuit breakers (or motor protectors), which protect each circuit from short circuits and overloads;
  • the KM contactors, which turn the motors on and off under control of the 24-volt circuit;
  • F-type thermal relays, which protect each motor from overload: they are set to the rated current and open their contacts when the motor draws more current than it should for too long;
  • the T auxiliary transformer and the 24-volt DC power supply for the PLC, the numerical control system, the sensors, and the solenoid valves;
  • the PLC (Chapter 49) and, in CNC machines, the servomotor drives and the spindle inverter (Chapters 45 and 48);
  • the ground bar, to which all of the machine's PE conductors are connected.
400 V 3-phase power supplyL1 L2 L3 + PEQ0 isolatorlockable main disconnect switchfuses andcircuit breakersKM powerpower contactorsF thermal relaysM 3-phase motorsspindle, pumpT transformer400 / 24 Vpower supply24 V DCPLCChapter 49ControlCoilsstopemergencyChapter 51buttons,limit switches, sensorsPLC inputs
Figure 44.22 · A block diagram of a machine tool. The solid arrows represent power, and the dashed arrows represent controls and signals.

The emergency stop

Every machine has one or more emergency stop buttons: mushroom-shaped, red on a yellow background, and accessible from every workstation. When pressed, they remain locked in place until they are turned or pulled. Their contacts are positive-opening NC: the button mechanically disengages them even if they have become stuck. The emergency stop cuts power to the motors immediately (stop category 0) or after controlled braking (category 1), and resetting it must never cause the machine to restart on its own: a new start command is required. In modern machines, the buttons are connected to a safety relay or a safety PLC; standards, categories, and circuits are covered in Chapter 51.

Reading a diagram: moving and stop with self-locking

The electrical diagram of a motor is drawn in two parts. The power diagram shows the path of the current that powers the motor: isolator or switch Q1, main contacts of contactor KM1, thermal relay F1, motor M1. The control diagram shows the 24-volt logic that determines when the KM1 coil is energized. In the diagrams, the contacts are always shown in their rest positions: coils are de-energized, and buttons are not pressed.

L1L2L3Q1KM1F1M3~PEPower Circuit24 V0 VF2S2EmergencyF1thermalS0stopS1runKM1111295961112131413KM11423KM124A1A2H1in motioncontrol circuit
Figure 44.23 · Starting and stopping a three-phase motor. On the left is the power supply; on the right is the control circuit, shown in a drawing between the two lines labeled 24 V and 0 V. The numbers next to the contacts are those printed on the component terminals.

The control circuit is read from top to bottom, like a path that the current must follow to reach the KM1 coil.

  • Fuse F2 protects the control circuit;
  • The emergency button S2 (NC 11-12), the thermal switch contact F1 (NC 95-96), and the emergency stop button S0 (NC 11-12) are connected in series: if even one of them opens, the coil loses power;
  • The S1 run button (NA 13-14) is connected in parallel with the KM1 auxiliary contact 13-14: this is the self-holding contact;
  • The H1 lamp, controlled by contacts 23 and 24 of KM1, indicates that the motor is running.
Example 44.28 · What happens, step by step
Press S1: Current passes through S2, F1, S0, and S1 and reaches the KM1 coil, which becomes energized
KM1 closes the three power contacts (the motor starts) and the auxiliary contacts 13-14 and 23-24 (H1 turns on)
S1 is released: the current now passes through contacts 13-14 of KM1, which are closed, and the coil remains energized on its own
When S0 is pressed: the circuit opens, KM1 de-energizes, opens all its contacts, and the motor stops; the latch also opens, so when S0 is released, the motor remains stopped
If the motor is overloaded, F1 opens to 95–96 and the same thing happens; if the mains voltage is lost, KM1 de-energizes, and when the voltage returns, the motor does not restart on its own
The autoretain feature converts a one-time command (press and release) into a sustained state, and provides free protection against unexpected reboots.
✅
Because the stop button has an NC contact. If a wire in the stop button breaks, an NC contact causes the circuit to open and the machine to stop: the failure leads to a safe condition. With an NO contact, the same broken wire would leave the machine running, and no one would notice until it was too late. The same logic, using both NO and NC contacts, is found in PLC ladder logic (Chapter 49).

44.15 The Formulas in This Chapter

WhatFormula
Current and ChargeI = Q / t · Q = I · t
Ohm's LawV = R · I
Resistance of a ConductorR = ρ · L / S
Resistance and TemperatureRT = R20 · (1 + α · ΔT)
Electrical powerP = V · I = R · I² = V² / R
EnergyE = P · t (kWh, where P is in kW and t is in hours)
SeriesReq = R1 + R2 + ...
Parallel1 / Req = 1 / R1 + 1 / R2 + ... · only two: R1 · R2 / (R1 + R2)
SplitterVu = V · R2 / (R1 + R2)
KirchhoffΣ Incoming = Σ Outgoing · Σ E = Σ R · I
Real GeneratorV = E − Ri · I · Icc = E / Ri
CapacitorQ = C · V · τ = R · C · vC = V · (1 − e−t/τ)
ElectromagnetismF = B · I · L · e = B · L · v
Sine Wavef = 1 / T · ω = 2π · f · V = Vp / √2
Reactances and ImpedanceXL = 2π · f · L · XC = 1 / (2π · f · C) · Z = V / I
Single-Phase Power RatingsS = V · I · P = V · I · cos φ · Q = V · I · sin φ · S² = P² + Q²
Power Factor CorrectionQC = P · (tan φ − tan φ') · C = QC / (ω · V²)
Three-phaseVL = √3 · VF · P = √3 · V · I · cos φ · S = √3 · V · I
Star and Trianglestar: IL = IF, V across the load = VL / √3 · triangle: IL = √3 · IF, V across the load = VL
TransformerV1 / V2 = N1 / N2 = I2 / I1
Ground in TT systemsRa · IΔn ≤ 50 V

44.16 Exercises

For copper, use ρ = 0.0175 Ω · mm²/m; for aluminum, use 0.028. Try it yourself before opening the solution.

Exercise 1. What is the current flowing through a 4.7 kΩ resistor supplied with 24 V?
Solution

I = 24 / 4700 = 0.005 11 A = 5.11 mA (or 24 V / 4.7 kΩ = 5.11 mA).

Exercise 2. A 24-volt sensor draws 15 mA. What is its equivalent resistance across the power supply?
Solution

R = 24 / 0.015 = 1,600 Ω = 1.6 kΩ.

Exercise 3. What is the resistance of a 120-meter-long aluminum conductor with a cross-sectional area of 16 mm²?
Solution

R = 0,028 · 120 / 16 = 0,21 Ω.

Exercise 4. A 25-meter-long, 230-volt single-phase copper wire (1.5 mm²) supplies a load that draws 10 A. What is the voltage drop, in volts and as a percentage?
Solution

Total wire length 50 m: R = 0.0175 · 50 / 1.5 = 0.583 Ω; ΔV = 0.583 × 10 = 5.83 V; 5.83 / 230 × 100 = 2.5%.

Exercise 5. A 60-watt soldering iron operates at 230 V. What is its current consumption, and what is its resistance?
Solution

I = 60 / 230 = 0,261 A; R = 230² / 60 = 52 900 / 60 = 881,7 Ω.

Exercise 6. A 12-kW tempering furnace operates 6 hours a day for 20 days a month. At an energy cost of 0.22 €/kWh, how much does it cost per month?
Solution

E = 12 × 6 × 20 = 1,440 kWh; cost = 1,440 × 0.22 = 316.80 € per month.

Exercise 7. Two resistors, one of 100 Ω and one of 150 Ω, connected in parallel, are in series with a 40 Ω resistor, all connected to a 24 V power source. Calculate the total current, the voltage across the parallel circuit, and the two currents in the parallel circuit.
Solution

In parallel: 100 × 150 / 250 = 60 Ω; total 60 + 40 = 100 Ω; I = 24 / 100 = 0.24 A; voltage across the parallel branch 60 · 0.24 = 14.4 V; currents 14.4 / 100 = 0.144 A and 14.4 / 150 = 0.096 A (sum 0.24 A).

Exercise 8. A voltage divider with R1 = 4.7 kΩ and R2 = 3.3 kΩ is supplied with 24 V. What is the open-circuit voltage across R2?
Solution

Vu = 24 · 3.3 / (4.7 + 3.3) = 24 · 3.3 / 8 = 9.9 V.

Exercise 9. 5 A and 2 A enter a node; 3 A exit a third wire. What is the current in the fourth wire?
Solution

Incoming: 5 + 2 = 7 A; outgoing: 3 A + I; I = 7 − 3 = 4 A, outgoing from the node.

Exercise 10. A 24 V battery measures 24.0 V when open-circuit and 23.2 V when delivering 20 A. Calculate the internal resistance and the short-circuit current.
Solution

Ri = (24.0 − 23.2) / 20 = 0.04 Ω; Icc = 24 / 0.04 = 600 A.

Exercise 11. A 220 µF capacitor is charged through a 47 kΩ resistor. What is the time constant? After how long can the capacitor be considered fully charged?
Solution

τ = 47,000 × 0.000 22 = 10.34 s; load after approximately 5τ = 51.7 s.

Exercise 12. Calculate the peak value of the 400-V linked voltage and that of a 24-V AC control voltage.
Solution

400 · 1,4142 = 565,7 V; 24 · 1,4142 = 33,9 V.

Exercise 13. A single-phase load draws 6 A at 230 V with a power factor of φ = 0.7. Calculate S, P, and Q.
Solution

S = 230 · 6 = 1380 VA; P = 1380 · 0.7 = 966 W; sin φ = √(1 − 0.49) = 0.714; Q = 1380 × 0.714 = 985.5 var. With cos φ = 0.7, the reactive power exceeds the active power: a case requiring power factor correction.

Problem 14. Three 23-Ω resistors are connected in a star configuration to a 400-V power system. Calculate the line current and the total power. How would this change if they were connected in a delta configuration?
Solution

Voltage across each resistor: 400 / 1.732 = 230.9 V; I = 230.9 / 23 = 10.04 A; P = 3 · 230.9² / 23 = 6,957 W ≈ 7.0 kW. In a delta configuration, the power would triple (approximately 20.9 kW) and the line current would also triple (30.1 A).

Exercise 15. A three-phase motor with a rated power of 4 kW at 400 V has η = 0.87 and cos φ = 0.82. What is its current draw at full load?
Solution

Pa = 4000 / 0,87 = 4598 W; I = 4598 / (1,732 · 400 · 0,82) = 4598 / 568,1 = 8,09 A.

Exercise 16. A 230/12 V transformer has 920 turns on the primary winding. How many turns does the secondary winding have? If the secondary winding delivers 5 A, how much current does the primary winding draw (ideal transformer)?
Solution

N2 = 920 × 12 / 230 = 48 turns; I1 = 5 × 12 / 230 = 0.261 A.

Exercise 17. What do an IP55 motor and an IP67 sensor guarantee? And why is the stop button an NC contact rather than an NA contact in the diagram shown in Figure 44.23?
Solution

IP55: Protected against dust (some dust may enter without causing damage) and water jets. IP67: Fully protected against dust and resistant to temporary immersion. The stop is NC because a fault (broken wire, loose terminal) opens the circuit and stops the machine: the fault leads to a safe condition, whereas with an NO, the same fault would leave the machine running.