Electrical Engineering
Every machine tool is also an electrical machine: the spindle is a motor, the axes are driven by servomotors, the numerical control and the PLC operate at 24 V, and everything is powered by a 400 V control panel. In this chapter, we’ll cover the basics: current, voltage, and resistance; Ohm’s law and Kirchhoff’s laws; power and energy; magnetism; alternating current and the three-phase system; and transformers. Then we’ll look at how to measure these quantities and, most importantly, how to protect ourselves, all the way to reading a motor’s start-stop sequence diagram. One rule applies throughout the entire chapter: only authorized personnel may work inside control panels, and only when the system is de-energized.
44.1 Charge, Current, and Voltage
Matter is made up of atoms, and each atom has a positively charged nucleus surrounded by negatively charged electrons. In metals, the outermost electrons are loosely bound and can move from one atom to another; this is why metals are conductors. In plastics, rubber, glass, and ceramics, the electrons remain in place: these materials are insulators, and they are used to coat cables and separate live parts.
The electric charge Q is measured in coulomb (C). A coulomb is an enormous number of electrons: approximately 6.24 × 1018. When charges move in an orderly manner within a conductor, this results in a electric current; its intensity I It is the charge that passes through a cross-section of the wire in one second, and is measured in ampere (A).
For charges to move, something must push them: voltage V (or potential difference), which is measured in volts (V). Voltage is the energy that the generator supplies to each coulomb that passes through it: 1 V = 1 J/C. A 12-volt battery supplies 12 joules per coulomb; the household electrical grid supplies 230 joules per coulomb.
The comparison with water is very helpful. The pump creates a pressure difference between the supply and return lines, and the water circulates through the circuit; the amount of water that passes through in one second is the flow rate. A narrow pipe slows down the water. In an electrical circuit, the generator creates voltage, the charges flow, the current is the “charge flow rate,” and the resistance is the narrow pipe.
Direct Current and Alternating Current
If the voltage always has the same value and direction, it is called direct current (symbol ⎓ or DC): this is the type found in batteries and power supplies. If, on the other hand, the voltage continuously changes in both magnitude and direction, following a curve called a sine wave, it is called alternating current (symbol ~ or AC): this is the type used in the electrical grid, which in Europe operates at 50 cycles per second.
A machine tool has both tools. The control panel receives a 400-volt three-phase AC supply, which powers the motors; a transformer and a power supply provide 24 volts DC for the PLC, the numerical control system, the sensors, the solenoid valves, and the contactor coils.
A charger delivers 2 A for an hour and a half. How much charge goes into the battery?
44.2 Electrical Circuits and Ohm's Law
An electrical circuit is a closed path through which current can flow. It always consists of a power source (cell, battery, power grid, power supply), conductors (wires), one or more loads (lamps, motors, resistors, coils), and usually a control device (switch, button, contact) and a protective device (fuse, circuit breaker).
- closed circuit: the path is complete and current flows;
- open circuit: the path is interrupted (an open switch, a broken wire) and no current flows, even though voltage is present;
- Short circuit: The two terminals of the generator come into contact through a resistance that is virtually zero; the current becomes extremely high, and without protection, the wires will melt or catch fire.
In schematics, each component is drawn with a standardized symbol. In Italy, the CEI EN 60617 standards apply, which are the same throughout Europe: anyone who learns to read them can understand schematics from any manufacturer. The figure shows the symbols we will use in this chapter.
The German physicist Georg Ohm discovered that in a metallic conductor, at a constant temperature, the current is directly proportional to the voltage: if the voltage doubles, the current also doubles. The ratio between voltage and current is constant and is called resistance R; it is measured in ohms (Ω).
A 24-volt indicator light has a resistance of 48 Ω: How much current does it draw?
A contactor coil, powered by 24 V DC, draws 0.2 A: What is its resistance?
A current of 5 mA flows through a 2.2 kΩ resistor: What is the voltage across it?
44.3 Resistance and Resistivity
The resistance of a wire depends on three factors: the material, the length, and the cross-sectional area. A long wire offers more resistance than a short one, and a thick wire offers less resistance than a thin one—just as a wide pipe allows more water to flow through than a narrow one. The material is represented in the formula by its resistivity, ρ (rho).
| Material | ρ at 20 °C (Ω · mm²/m) | α (1/°C) | Where it is used |
|---|---|---|---|
| Silver | 0,016 | 0,0038 | relay and switch contacts |
| Copper | 0,0175 | 0,0039 | cables, windings, busbars |
| Aluminum | 0,028 | 0,0040 | large-diameter lines, motor enclosures |
| Brass | 0,07 | 0,0015 | terminals, plugs |
| Structural steel | 0,15 | 0,005 | structures, frames, rebar grounding conductors |
| Stainless steel | 0,72 | 0,001 | machine parts, braking resistors |
| Nickel-chromium | 1,1 | 0,0001 | heating elements |
Approximate, rounded values: for steels, these vary significantly depending on the composition.
A 2.5 mm² copper cable is 50 m long. What is the resistance of a single conductor? And what about the combined resistance of the supply and return lines? What if it were made of aluminum?
The voltage drop across a line
Power cables are also resistors—small ones, but not zero. When current flows through them, a voltage is “lost” across them R · I, and the load receives less voltage than at the start. It is the voltage drop: If it is too high, the motors have trouble starting, the lights are dim, and the wires overheat. For consumer circuits, the goal is to stay within 4% of the rated voltage.
A 3-kW, 230-V heater is powered by a 40-meter run of 2.5-mm² copper wire. How much voltage is lost along the line? And with a 4-mm² wire?
The Effect of Temperature
In metals, resistance increases with temperature. For relatively small changes, the increase is proportional to the change in temperature, with the coefficient α shown in the table. This is why a hot motor has higher resistance in its windings than a cold one, and why manufacturers estimate the temperature of the windings by measuring their resistance.
One phase of a motor measures 2.0 Ω at 20 °C. What is the reading when the winding is at 80 °C?
44.4 Power and Electrical Energy
The generator delivers V joules per coulomb, and I coulombs pass through in one second: the energy delivered in one second—that is, the power—is the product of V and I. Using Ohm's law, this same power can be expressed in two other ways, which are convenient when the resistance is known.
In a resistor, all electrical energy is converted into heat: this is the Joule effect. It is useful in heating elements, heat-treatment furnaces (Chapter 22), and soldering irons; it is also useful in fuses, where a thin wire melts when the current exceeds the limit. On the other hand, it is a waste in cables, motors, and transformers, where it generates heat without performing any useful work. The formula R · I² reveals an important fact: doubling the current quadruples the heat.
An electric space heater is rated at 2000 W at 230 V. What is its current draw, and what is its resistance?
Based on Example 44.4 (0.56 Ω, 13.04 A), how much power is converted into heat in the cables?
Energy and the kilowatt-hour
Energy is power times time. In the SI system, it is measured in joules, but for electricity, the kilowatt-hour (kWh) is used—the energy of 1 kW over one hour, equal to 3.6 MJ (Chapter 2). This is the unit shown on the meter and on the bill.
The workshop's compressor draws 3 kW and runs an average of 5 hours a day for 220 days a year. At an electricity rate of 0.25 €/kWh, how much does it cost per year? And how much do 20 36-W LED ceiling lights cost if left on for a weekend (60 hours)?
44.5 Resistors in Series and in Parallel
Two or more resistors are in series when they are connected one after the other along the same path: the current is the same through all of them, and the generator’s voltage is divided among them. They are in parallel when they are connected to the same two points: they all have the same voltage, and the generator’s current is divided among them. The outlets in a home and the loads on a circuit breaker panel are connected in parallel: each receives the full voltage and operates even if the others are turned off.
10-, 22-, and 68-Ω resistors connected in series across 24 V. What are the current and voltage across each one?
60-, 40-, and 120-Ω resistors connected in parallel across 24 V. What are the equivalent resistance and currents?
A resistor R1 = 10 Ω is connected in series with the parallel combination of R2 = 30 Ω and R3 = 60 Ω; the entire circuit is powered by 12 V. What are the currents and voltages?
The Voltage Divider
Two resistors connected in series divide the voltage into parts proportional to their values. By measuring the voltage across just one of the two resistors, you obtain a voltage lower than the original one: this is a voltage divider. It is used to match a signal to the input of an electronic circuit, and is found inside sensors and potentiometers (Chapter 47).
If R1 = 3.9 kΩ and R2 = 1 kΩ, what voltage is obtained from 24 V? And what if a 10 kΩ load is connected to the output?
44.6 Kirchhoff's Laws and the Real Generator
When a circuit has multiple generators or multiple interlinked loops, series and parallel connections alone are not enough. You need Kirchhoff's two laws, which apply to any circuit.
- Node Theorem. A node is a point where three or more files meet. Charges do not accumulate: the sum of the currents entering a node is equal to the sum of the currents leaving it.
- Mesh Law. A mesh is a closed path within the circuit. When tracing a path along a mesh, the sum of the voltages across the generators is equal to the sum of the voltage drops R · I across the resistors.
In the circuit shown in Figure 44.9, E1 = 24 V with R1 = 4 Ω, E2 = 12 V with R2 = 2 Ω, and R3 = 6 Ω. Find the three currents.
The Real Generator
An ideal generator would always produce the same voltage, regardless of the current demanded of it. A real generator has a small internal resistance, Ri: when it supplies current, part of the voltage is lost internally, and less voltage reaches the terminals. The voltage when there is no load is called the electromotive force, E.
A 12 V battery measures 12.6 V when open-circuit and 12.0 V when delivering 10 A. What is its internal resistance? What current would it supply in a short-circuit condition?
44.7 Capacitors and Inductors
A capacitor consists of two conductive surfaces, called plates, separated by an insulator. When connected to a voltage, it accumulates a positive charge on one plate and a negative charge on the other, and retains these charges even when disconnected. The accumulated charge is proportional to the voltage; the ratio between the two is the capacitance C, which is measured in farads (F). A farad is an extremely large unit: in practice, microfarads (1 µF = 10−6 F) and nanofarads are used.
A capacitor does not charge instantly. If it is charged through a resistor R, the voltage rises rapidly at first and then more and more gradually, following an exponential curve. The characteristic time is the time constant τ = R · C: after τ, the capacitor is at 63% of its final voltage; after 3τ, at 95%; after 5τ, at 99%; and it is considered fully charged. Discharging follows the inverse curve: after τ, 37% of the voltage remains.
A 100 µF capacitor is charged to 24 V through a 10 kΩ resistor. Calculate τ, the voltage after 1 s and after 5 s, the time it takes to reach 12 V, and the final charge.
Capacitors are found in power supplies, where they smooth out the voltage; in timing circuits; on single-phase motors, to start them; and in power factor correction panels (section 44.10). And in frequency converters (inverters, Chapter 45), which contain large capacitors charged to more than 500 V.
The inductor, as a brief mention
An inductor is a coil of file, often wound around an iron core. It behaves in the opposite way to a capacitor: it resists changes in current. When it is energized, the current rises slowly, with a time constant τ = L / R; when the circuit is opened, the coil tries to maintain the current and produces a voltage spike that can cause sparks at the contacts and damage electronic components. For this reason, the coils of DC relays and solenoid valves have a diode connected in parallel, while those for AC have an RC filter (Chapters 46 and 49). Inductance L is measured in henry (H).
44.8 Magnetism and Electromagnetism
A magnet has two poles, north and south: like poles repel each other, and opposite poles attract each other. A magnetic field surrounds the magnet, represented by a drawing of lines that emerge from the north pole and return to the south pole; where the lines are dense, the field is strong. The strength of the field is measured by the magnetic induction B, in tesla (T): between the poles of a motor, it reaches about 1 T, while a refrigerator magnet has a few hundredths of a tesla.
In 1820, it was discovered that an electric current also creates a magnetic field around the wire. When the wire is wound into a coil, the magnetic lines of force add up, and the coil behaves like a magnet that turns on and off with the current. This gives rise to two effects that drive the entire world of electricity.
- Force on a conductor. A current-carrying wire placed in a magnetic field experiences a force that is perpendicular to both the wire and the field. This is the principle of the engine: The rotor's slots contain conductors through which current flows, and the forces generate torque.
- Electromagnetic induction. A wire moving within a magnetic field, or a coil in which the field changes, generates a voltage across its ends. This is the principle behind the generator (and, as we will see, the transformer). The direction of the induced voltage is always such that it opposes the cause that produced it: a generator under load slows down whatever is causing it to rotate.
A 0.15 m-long conductor in a 0.8 T magnetic field carries a current of 20 A. What force acts on it? If, instead, it is moved at 10 m/s without current, what voltage is induced?
Electromagnets, Relays, and Contactors
A coil wound around a soft-iron core is an electromagnet: when current flows through it, it attracts iron; when the current is off, it repels it. Solenoid valves in pneumatics and hydraulics (Chapters 42 and 43), motor brakes, and the magnetic plates in grinders all work this way.
The relay uses an electromagnet to move contacts. The coil, powered by a small current (often 24 V), attracts a movable armature that shifts the common contact C: at rest, C touches the NC contact; when the coil is energized, it switches to the NO contact. In this way, a low-voltage control circuit turns another, separate circuit on and off. A contactor is a heavy-duty relay with three power contacts capable of controlling a motor and several auxiliary contacts for control signals.
44.9 Sinusoidal Alternating Current
A generator that rotates a coil within a magnetic field produces a voltage that rises, falls, changes polarity, and returns, following a sine wave. This is the waveform of the line voltage. There are only a few parameters that describe it.
- the period T, the duration of a complete cycle, in seconds;
- the frequency f, the number of cycles per second, in hertz (Hz): in Europe, the power grid operates at 50 Hz; in North America, at 60 Hz;
- the peak value Vp, the maximum value reached;
- the effective value V, the value of the DC voltage that would heat a resistor in the same way. This is the value we always refer to: “230 V” is an effective value, and it is what multimeters measure.
Resistive, Inductive, and Capacitive Loads
Each load behaves differently, depending on its nature.
- Resistive load (light switches, ovens, incandescent lamps): the current follows the voltage instant by instant; it is said to be in phase.
- Inductive load (motors, transformers, coils, reactors): The coil dampens fluctuations, and the current lags behind the voltage. The coil presents an inductive reactance XL that increases with frequency.
- Capacitive load (capacitors): The current leads the voltage; the capacitive reactance XC decreases as the frequency increases.
The lag or lead is measured by the phase angle φ (phi), in degrees: a full cycle is 360°. A real load, such as a motor, is somewhat resistive and somewhat inductive: the current lags by an angle between 0° and 90°. The ratio of the rms voltage to the rms current is called impedance Z, in ohms.
What is the current, at 230 V and 50 Hz, flowing through an ideal 0.1 H coil? And through a 10 µF capacitor?
44.10 AC Power and Power Factor
When current and voltage are out of phase, the product V × I is no longer entirely useful work. A portion of the energy flows back and forth between the grid and the magnetic fields of the coils (or capacitors) without being converted into work or heat. Thus, three types of power are distinguished.
- active power P, in watts (W): the power that is actually converted into mechanical work or heat, and which the meter measures in kWh;
- reactive power Q, in reactive volt-amperes (var): the power needed to create the magnetic fields in motors and transformers, which is fed back;
- apparent power S, in volt-amperes (VA): the product of the effective voltage and current. Cables, circuit breakers, transformers, and generators are sized based on this value, because they are the components that carry the current.
A low power factor is a problem: for the same active power, the current is higher, so the cables get hotter, voltage drops increase, and the substation transformer reaches its capacity sooner. For this reason, the utility charges for reactive power when the average power factor falls below the values established by the electric utility’s regulations. The solution is power factor correction: capacitors are connected in parallel with the inductive loads. The capacitors absorb reactive power of the opposite sign and supply it “on the spot” to the motors, so less current passes through the grid. In industrial settings, power factor correction is usually performed using an automatic control panel that connects the capacitors in stages.
A single-phase motor draws 10 A at 230 V with cos φ = 0.8. Calculate S, P, and Q. What kind of capacitor is needed to bring cos φ to 0.95, and how much current will it draw afterward?
44.11 The Three-Phase System
The power grid carries not just one alternating voltage but three, generated by a generator with three windings shifted by 120°. The three voltages have the same frequency and the same magnitude, but they are out of phase by 120° relative to each other, that is, by one-third of a period: 20 / 3 = 6.67 ms. They travel along three phase conductors, L1, L2 e L3, plus a conductor of neutral N grounded in the cabin, and a PE protective conductor.
The voltage between a phase and the neutral is 230 V; the voltage between two phases is 400 V. The ratio between the two is not 2, because the voltages are out of phase: it is √3 = 1.732. Three-phase power has two major advantages: it transmits more power using the same amount of copper, and it produces a rotating magnetic field in motors that allows them to start and run on their own, without capacitors or brushes (Chapter 45).
Star and Delta Connections
Three identical loads—for example, the three windings of a motor or the three heating elements of an oven—can be connected to the power grid in two ways.
- Star (Y) connection: The three loads share one end (the star point, which can be connected to the neutral) and have their other ends connected to a phase. Each load receives the phase voltage, 230 V; the line current is equal to the load current.
- Triangular (Δ): Each load is connected between two phases. Each load receives the phase-sequence voltage, 400 V; the line current is √3 times the load current.
An oven has three 46 Ω heating elements. What is the current and power drawn from a 400 V power source when the oven is connected in a star configuration and when it is connected in a delta configuration?
Three-Phase Power
A 7.5 kW three-phase asynchronous motor (shaft power) operates at 400 V with an efficiency of η = 0.90 and a power factor of cos φ = 0.84. What is its current draw at full load?
44.12 The Transformer and Measuring Instruments
A transformer changes the value of an alternating voltage. It consists of two windings—the primary and the secondary—wound around the same iron-sheet core and insulated from each other. The alternating current in the primary winding creates a magnetic flux in the core that changes continuously; this flux also passes through the secondary winding and, by induction, induces a voltage there. Each turn has the same induced voltage, so the voltages are in the same ratio as the number of turns. With direct current, the flux does not change and the transformer does not function.
In a machine, a 250 VA transformer connected between two phases supplies 24 V AC to the control circuits. The primary winding has 800 turns. Calculate the turns ratio, the number of turns in the secondary winding, and the full-load currents.
In machine control panels, the auxiliary transformer serves two purposes: it steps down the voltage and isolates the control circuits from the mains. This ensures that any malfunction involving the buttons or limit switches occurs at 24 V—a much less dangerous voltage—and that the circuit has its own controlled ground connection.
The multimeter and the clamp meter
A multimeter (or tester) measures voltage, current, and resistance—both DC and AC—and usually also checks for continuity in a wire by emitting an audible signal. The way you connect it depends on the quantity being measured, and connecting it incorrectly can be dangerous.
- Voltage (V⎓ or V~): The probes should be placed on the two points between which you want to measure the voltage—that is, in parallel. The voltmeter has a very high internal resistance (several MΩ) and does not interfere with the circuit.
- Current (A): Open the circuit and connect the meter in series, with the red probe in the current terminal. The ammeter has an internal resistance that is virtually zero.
- Resistance (Ω) and continuity: The component must be de-energized; it is best to disconnect it from the rest of the circuit; the meter uses its internal battery.
The current collet measures alternating current (and, with the appropriate models, direct current as well) without breaking the circuit: the jaws clamp around the wire and detect the magnetic field that the current creates around it. The collets must clamp only a single conductor: if they clamp both the live wire and the neutral wire together, the two currents are equal and opposite, and the collet meter reads zero. It is the right tool for checking how much power a motor draws.
A multimeter was left with its probes in the current terminals, and someone plugged it into a 230 V outlet to “see if there’s voltage.” The internal resistance in that position, including the probes, is about 0.1 Ω. How much current would it draw?
44.13 Electrical Safety
Electric current that travels through the human body disrupts the muscles and the heart—which function using small electrical signals—and burns tissue. The extent of the damage depends primarily on theintensity of the current and from the duration, then by the path (the hands and feet pass through the heart) and by the frequency. The table provides an idea of the thresholds for 50-Hz alternating current.
| Electric Current in the Body | Typical Effects |
|---|---|
| about 0.5 mA | threshold of perception: a tingling sensation |
| about 10 mA | release threshold: above this value, the muscles contract and you can no longer lift your hand |
| 20–30 mA | contraction of the chest muscles, difficulty breathing if the contact continues |
| more than 50 mA | risk of cardiac fibrillation, which increases the longer the contact lasts |
| more than 1 A | stop of heart function, severe internal and external burns |
Approximate and rounded values: Sensitivity varies from person to person and depending on the duration of contact.
The current that flows depends on the voltage and the body’s resistance, which is not constant: it decreases as the voltage increases, when the skin is wet or sweaty, and when there is a large contact area. For this reason, standards establish a limit for contact voltage: in ordinary environments, 50 V for alternating current and 120 V for direct current. Below these values, contact—even prolonged contact—is not considered dangerous.
Using conservative estimates, at 230 V, the body’s resistance between the hands and feet can be estimated at around 1,000 Ω; at 24 V, with dry skin, around 3,000 Ω. How much current flows?
Direct and Indirect Contacts
- Direct contact: You touch a part that is live during normal operation, such as an exposed terminal or a stripped wire. Protection is provided by insulation, enclosures, barriers, physical distance, and locking control panels. The 30-mA ground-fault circuit interrupter (GFCI) provides an additional layer of protection.
- Indirect contact: You touch a metal part—such as a motor housing, a control panel door, or a machine base—that is normally de-energized but has become energized due to a failure in the insulation. This is the most insidious type, because the person touching it has done nothing wrong. Protection is provided by grounding the metal parts in conjunction with a ground-fault circuit interrupter (GFCI).
Grounding connects all ground points, via the yellow-green PE protective conductor, to a grounding rod driven into the ground. If the live wire comes into contact with the chassis, the fault current finds a path to ground and returns to the substation; the ground-fault circuit interrupter detects this and breaks the circuit before anyone gets hurt.
In the case of Figure 44.21, the machine’s ground resistance is Ra = 20 Ω and the cabin’s ground resistance is Rn = 5 Ω. What current does the fault flow? What is the voltage across the housing? Will a 16 A circuit breaker trip?
Residual Current Device (RCD) and Circuit Breaker
The ground-fault circuit interrupter (GFCI) routes all live conductors (phase and neutral, or the three phases and neutral) through an iron ring, the toroid. If everything is working properly, the incoming and outgoing currents are equal, and their magnetic fields cancel each other out. If part of the current leaks to ground—through a metal object or a person—the balance is lost: a current flow is generated in the toroid, a small winding detects it, and the circuit breaker trips. The 30 mA IΔn sensitivity is used as additional protection for people. The RCD has a test button labeled “T,” which should be pressed periodically: if it does not trip, it must be replaced.
The circuit breaker, on the other hand, protects cables and appliances from excessively high currents and has two trip mechanisms.
- the thermal cut-off, a bimetallic strip that heats up and bends: it trips in response to overloads (currents slightly above the rated value), with the response time becoming shorter as the current increases;
- The magnetic trip unit, a coil that attracts an armature: it responds to short circuits in a few thousandths of a second.
| Curve | Magnetic response (multiples of In) | Typical Use |
|---|---|---|
| B | 3 to 5 times | long lines, resistive loads, outlets |
| C | 5 to 10 times | General-purpose, small motors, lighting |
| D | 10 to 20 times | transformers and motors with high inrush current |
Earth-leakage circuit breakers and circuit breakers with thermal-magnetic protection serve two different purposes: the former protects people from electric shocks, while the latter protects the electrical system from overcurrents. They are often combined into a single device, the earth-leakage circuit breaker with thermal-magnetic protection. Fuses perform the same function as circuit breakers by melting: gG-type fuses protect circuits, while aM-type fuses are designed for motors, which draw five to eight times the rated current for a few seconds during startup.
IP Protection Ratings
The enclosures of control panels, motors, push-button panels, and sensors are marked with an IP code followed by two digits (CEI EN 60529 standard). The first digit indicates the degree of protection against the ingress of solid objects and contact with internal parts; the second digit indicates the degree of protection against water. An “X” in place of a digit means that test was not performed.
| Figure | First section: solid figures | Second digit: water |
|---|---|---|
| 0 | no protection | no protection |
| 1 | objects larger than 50 mm (the back of the hand) | drops falling vertically |
| 2 | objects larger than 12.5 mm (a finger) | drops with a slanted casing up to 15° |
| 3 | objects larger than 2.5 mm (one tool) | rain at an angle of up to 60° from the vertical |
| 4 | objects larger than 1 mm (a wire) | splashes from all directions |
| 5 | dust-protected (a small amount of dust can enter without causing damage) | water jets |
| 6 | completely dust-proof | powerful jets |
| 7 | temporary immersion | |
| 8 | continuous dive, under the specified conditions | |
| 9 | high-pressure, high-temperature jets |
44.14 The Machine Tool's Electrical Panel
All of a machine’s electrical equipment originates from its control panel, which is designed in accordance with the CEI EN 60204-1 standard. As the current flows from the power grid to the motors, the same components are always encountered.
- the main disconnect switch Q0, with the handle on the door: it cuts power to the entire machine and locks in the open position with a padlock, so no one can turn it back on during maintenance;
- fuses and circuit breakers (or motor protectors), which protect each circuit from short circuits and overloads;
- the KM contactors, which turn the motors on and off under control of the 24-volt circuit;
- F-type thermal relays, which protect each motor from overload: they are set to the rated current and open their contacts when the motor draws more current than it should for too long;
- the T auxiliary transformer and the 24-volt DC power supply for the PLC, the numerical control system, the sensors, and the solenoid valves;
- the PLC (Chapter 49) and, in CNC machines, the servomotor drives and the spindle inverter (Chapters 45 and 48);
- the ground bar, to which all of the machine's PE conductors are connected.
The emergency stop
Every machine has one or more emergency stop buttons: mushroom-shaped, red on a yellow background, and accessible from every workstation. When pressed, they remain locked in place until they are turned or pulled. Their contacts are positive-opening NC: the button mechanically disengages them even if they have become stuck. The emergency stop cuts power to the motors immediately (stop category 0) or after controlled braking (category 1), and resetting it must never cause the machine to restart on its own: a new start command is required. In modern machines, the buttons are connected to a safety relay or a safety PLC; standards, categories, and circuits are covered in Chapter 51.
Reading a diagram: moving and stop with self-locking
The electrical diagram of a motor is drawn in two parts. The power diagram shows the path of the current that powers the motor: isolator or switch Q1, main contacts of contactor KM1, thermal relay F1, motor M1. The control diagram shows the 24-volt logic that determines when the KM1 coil is energized. In the diagrams, the contacts are always shown in their rest positions: coils are de-energized, and buttons are not pressed.
The control circuit is read from top to bottom, like a path that the current must follow to reach the KM1 coil.
- Fuse F2 protects the control circuit;
- The emergency button S2 (NC 11-12), the thermal switch contact F1 (NC 95-96), and the emergency stop button S0 (NC 11-12) are connected in series: if even one of them opens, the coil loses power;
- The S1 run button (NA 13-14) is connected in parallel with the KM1 auxiliary contact 13-14: this is the self-holding contact;
- The H1 lamp, controlled by contacts 23 and 24 of KM1, indicates that the motor is running.
44.15 The Formulas in This Chapter
| What | Formula |
|---|---|
| Current and Charge | I = Q / t · Q = I · t |
| Ohm's Law | V = R · I |
| Resistance of a Conductor | R = ρ · L / S |
| Resistance and Temperature | RT = R20 · (1 + α · ΔT) |
| Electrical power | P = V · I = R · I² = V² / R |
| Energy | E = P · t (kWh, where P is in kW and t is in hours) |
| Series | Req = R1 + R2 + ... |
| Parallel | 1 / Req = 1 / R1 + 1 / R2 + ... · only two: R1 · R2 / (R1 + R2) |
| Splitter | Vu = V · R2 / (R1 + R2) |
| Kirchhoff | Σ Incoming = Σ Outgoing · Σ E = Σ R · I |
| Real Generator | V = E − Ri · I · Icc = E / Ri |
| Capacitor | Q = C · V · τ = R · C · vC = V · (1 − e−t/τ) |
| Electromagnetism | F = B · I · L · e = B · L · v |
| Sine Wave | f = 1 / T · ω = 2π · f · V = Vp / √2 |
| Reactances and Impedance | XL = 2π · f · L · XC = 1 / (2π · f · C) · Z = V / I |
| Single-Phase Power Ratings | S = V · I · P = V · I · cos φ · Q = V · I · sin φ · S² = P² + Q² |
| Power Factor Correction | QC = P · (tan φ − tan φ') · C = QC / (ω · V²) |
| Three-phase | VL = √3 · VF · P = √3 · V · I · cos φ · S = √3 · V · I |
| Star and Triangle | star: IL = IF, V across the load = VL / √3 · triangle: IL = √3 · IF, V across the load = VL |
| Transformer | V1 / V2 = N1 / N2 = I2 / I1 |
| Ground in TT systems | Ra · IΔn ≤ 50 V |
44.16 Exercises
For copper, use ρ = 0.0175 Ω · mm²/m; for aluminum, use 0.028. Try it yourself before opening the solution.
Solution
I = 24 / 4700 = 0.005 11 A = 5.11 mA (or 24 V / 4.7 kΩ = 5.11 mA).
Solution
R = 24 / 0.015 = 1,600 Ω = 1.6 kΩ.
Solution
R = 0,028 · 120 / 16 = 0,21 Ω.
Solution
Total wire length 50 m: R = 0.0175 · 50 / 1.5 = 0.583 Ω; ΔV = 0.583 × 10 = 5.83 V; 5.83 / 230 × 100 = 2.5%.
Solution
I = 60 / 230 = 0,261 A; R = 230² / 60 = 52 900 / 60 = 881,7 Ω.
Solution
E = 12 × 6 × 20 = 1,440 kWh; cost = 1,440 × 0.22 = 316.80 € per month.
Solution
In parallel: 100 × 150 / 250 = 60 Ω; total 60 + 40 = 100 Ω; I = 24 / 100 = 0.24 A; voltage across the parallel branch 60 · 0.24 = 14.4 V; currents 14.4 / 100 = 0.144 A and 14.4 / 150 = 0.096 A (sum 0.24 A).
Solution
Vu = 24 · 3.3 / (4.7 + 3.3) = 24 · 3.3 / 8 = 9.9 V.
Solution
Incoming: 5 + 2 = 7 A; outgoing: 3 A + I; I = 7 − 3 = 4 A, outgoing from the node.
Solution
Ri = (24.0 − 23.2) / 20 = 0.04 Ω; Icc = 24 / 0.04 = 600 A.
Solution
τ = 47,000 × 0.000 22 = 10.34 s; load after approximately 5τ = 51.7 s.
Solution
400 · 1,4142 = 565,7 V; 24 · 1,4142 = 33,9 V.
Solution
S = 230 · 6 = 1380 VA; P = 1380 · 0.7 = 966 W; sin φ = √(1 − 0.49) = 0.714; Q = 1380 × 0.714 = 985.5 var. With cos φ = 0.7, the reactive power exceeds the active power: a case requiring power factor correction.
Solution
Voltage across each resistor: 400 / 1.732 = 230.9 V; I = 230.9 / 23 = 10.04 A; P = 3 · 230.9² / 23 = 6,957 W ≈ 7.0 kW. In a delta configuration, the power would triple (approximately 20.9 kW) and the line current would also triple (30.1 A).
Solution
Pa = 4000 / 0,87 = 4598 W; I = 4598 / (1,732 · 400 · 0,82) = 4598 / 568,1 = 8,09 A.
Solution
N2 = 920 × 12 / 230 = 48 turns; I1 = 5 × 12 / 230 = 0.261 A.
Solution
IP55: Protected against dust (some dust may enter without causing damage) and water jets. IP67: Fully protected against dust and resistant to temporary immersion. The stop is NC because a fault (broken wire, loose terminal) opens the circuit and stops the machine: the fault leads to a safe condition, whereas with an NO, the same fault would leave the machine running.